IDEC FC6A-C16K1CE Communications Manual page 10

Fc6a series microsmart all-in-one type
Hide thumbs Also See for FC6A-C16K1CE:
Table of Contents

Advertisement

1: G
I
ENERAL
NFORMATION
Communication Cartridge
The communication cartridges can only be used when connected to cartridge slots 1 and 2 of the CPU module.
This port can be used to communicate with RS232C/RS485 communication-compatible external devices such as computers,
operator interfaces, and printers. Maintenance communication, user communication, Modbus RTU communication (master/slave),
and data link communication (master station/slave station) are possible.
Type No.
Electrical Characteristics
Maximum Communication Speed
Communication Functions
Maximum Cable Length
Isolation between Internal Circuit
Recommended
Cable
Cable
CAN Port
The CAN J1939 All-in-One Type can use this port to perform J1939 communication.
Communication Type
Communication Speed
Communication Functions
Connector
Cable
Maximum Cable Length
Terminating Resistance
Isolation between Internal Circuit
HMI-Ethernet Port
The HMI-Ethernet port can only be used when a CPU module and an HMI module are connected.
This port can be used to communicate with Ethernet communication-compatible external devices such as computers and operator
interfaces.
This port has eight connections that can be used with Ethernet communication. Each connection can be configured for
maintenance communication (server).
This port also supports the web server function and the send E-mail function.
Communication Type
Communication Speed
Number of Connections
Communication Mode
Web Server Function
Web Data Storage
System Web Page
Web Data
Web Page Editor
Capacity
Area Available to User 2.5 MB
Send E-mail Function
Connector
Cable
Maximum Cable Length
Isolation between Internal Circuit
When accessing the FC6A Series MicroSmart over the Internet, adequate security measures for the network to prevent
Caution
unauthorized access are required. Be sure to consult your network administrator or Internet service provider. IDEC bears
no responsibility for damages or problems caused due to security in Ethernet communication.
Restrict the access to FC6A Series MicroSmart with IP addresses and ports by using appropriate measures such as the
firewall.
1-2
EIA RS232C
115,200 bps
Maintenance communication, user communication, Modbus communication, data link communication
5 m
Not isolated
Shielded multicore: 24 AWG
CAN bus communication
250 kbps
J1939 communication
FC6A-PMTE05PN02
SAE-J1939-11
SAE-J1939-15
SAE-J1939-11
SAE-J1939-15
120 Ω (0.5 W or higher)
Power supply:
Signal:
IEEE 802.3 compliant
10BASE-T, 100BASE-TX
8 maximum
Maintenance Communication
Yes
FROM
Used
Used
Yes
RJ45
CAT 5. STP or higher
100 m
Pulse transformer isolated
FC6A S
M
S
A
ERIES
ICRO
MART
LL
FC6A-PC1
: Shielded twisted-pair
: Unshielded twisted-pair
: 40 m, stub 1 m maximum
: 40 m, stub 3 m maximum
Transformer isolated
Galvanic isolation, photocoupler isolated
Used
Not used
4.5 MB
-
-O
T
C
IN
NE
YPE
OMMUNICATION
FC6A-PC3
EIA RS485
115,200 bps
200 m
Not isolated
Shielded twisted-pair: 24 AWG
Not used
Not used
Used
Not used
3.0 MB
5.0 MB
M
FC9Y-B1730