■ Web Server Settings
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(1) Enable Web Server
Uncheck to disable Web server functions of the FC6A Series MicroSmart. Password authentication will be required when
accessing the web page.
When the Web server is enabled, you will be asked to enter a user name and password. You can access the Web server once
you enter the correct user name and the password on the dialog box shown on the browser.
When this is unchecked, the Web server port remains closed, and connection to the Web server using the Web browser is
prohibited.
(2) Web Server Port
Specify the port number for the Web server of the FC6A Series MicroSmart. The default port number is 80.
■ User Settings
(3) Use single user account to access web server
User Name :
Specify the user name used for authentication. The default user name is "administrator."
Password :
Specify the password used for authentication. The default password is "password." The password is shown
as * in the dialog box.
(4) Configure access privileges with multiple user accounts for web server
Select to use multiple accounts and limit access to the web server. Click Configure and create user accounts in the displayed
User Account Configuration dialog box. For details, see "User Account Settings" on page 11-4.
■ Web Page
(5) Enable Data Register Monitoring
Select this check box when using data register monitoring by embedding metacharacters in the html page and when using the
graph library. Valid for only files with the extension htm and html.
(6) Monitoring Interval (ms)
When monitoring, set the interval in ms to send requests from the web browser to the FC6A Series MicroSmart.
(7) Trend Monitor Interval (ms)
When performing monitoring that uses the trend graph, set the interval in milliseconds to send requests from the web browser
to the FC6A Series MicroSmart as a whole number multiple of the monitoring interval.
■ Options
(8) Redirect Target
To redirect the web page to the system web top page after displaying the system top page, select System Web Top Page.
Select Disable Redirect to disable redirect. Redirect may not work depending on each Web browser.
(9) Use System Web Page
Select this check box to use the system web pages.