Special Data Register

Special Data Register Device Addresses
Do not write to data in the area marked as reserved in the special data registers list. Otherwise the system may not operate
Warning
correctly.
Note: R/W is an abbreviation for read/write.
The notation for the R/W field is as follows.
R/W: The device can be both read from and written to
R: Read-only
W: Write-only
Device
Address
D8000
Quantity of Inputs
D8001
Quantity of Outputs
D8002
CPU Module Type Information
D8003
— Reserved —
D8004
D8005
General Error Code
D8006
User Program Execution Error Code
D8007
— Reserved —
D8008
D8009
D8010
Calendar/Clock Current Data
D8011
(Read only)
D8012
D8013
D8014
D8015
D8016
D8017
Calendar/Clock New Data
D8018
(Write only)
D8019
D8020
D8021
D8022
D8023
Scan Time Data
D8024
D8025
D8026
Communication Mode Information (Port 1 to Port 3)
D8027
— Reserved —
D8028
D8029
System Software Version
D8030
Communication Adapter Information
D8031
Optional Cartridge Connection Information
D8032
Interrupt Input Jump Destination Label No. (I1)
D8033
Interrupt Input Jump Destination Label No. (I3)
D8034
Interrupt Input Jump Destination Label No. (I4)
D8035
Interrupt Input Jump Destination Label No. (I6)
D8036
Timer Interrupt Jump Destination Label No.
D8037
Number of Connected I/O Modules
D8038 to
— Reserved —
D8051
D8052
J1939 Communication Error Code
D8053 to
— Reserved —
D8055
D8056
Battery Voltage
Description
Year
Month
Day
Day of the Week
Hour
Minute
Second
Year
Month
Day
Day of the Week
Hour
Minute
Second
Constant Scan Time Preset Value (1 to 1,000 ms)
Scan Time Current Value (ms)
Scan Time Maximum Value (ms)
Scan Time Minimum Value (ms)
FC6A S
M
S
A
ERIES
ICRO
MART
LL
-
-O
T
C
IN
NE
YPE
OMMUNICATION
Update Timing
When I/O initialized
When I/O initialized
Power-up
When error occurred
When error occurred
Every 500 ms
Every 500 ms
Every 500 ms
Every 500 ms
Every 500 ms
Every 500 ms
Every 500 ms
Every scan
At occurrence
At occurrence
Every scan
Power-up
Power-up
Power-up
When I/O initialized
Every scan
M
FC9Y-B1730
ANUAL
2: D
EVICE
R/W
R
R
R
-
R/W
R
-
R
R
R
R
R
R
R
W
W
W
W
W
W
W
W
R
R
R
R
-
R
R
R
R/W
R/W
R/W
R/W
R/W
R
R/W
R