User Communication Transmit Instruction Dialog Box in WindLDR
Selections and Devices in Transmit Instruction Dialog Box
TXD
Type
RXD
Port No.
Port 1 - Port 3
S1
Source 1
D1
Destination 1
D2
Destination 2
FC6A S
Transmit instruction
Receive instruction
Transmit user communication from port 1 (TXD1) through port 3 (TXD3)
Enter the data to transmit in this area.
Transmit data can be constant values (character or hexadecimal), data registers, or BCC.
Transmit completion output can be an output or internal relay.
Transmit status register can be data register D0000-D7998 or D10000-D55998.
The next data register stores the byte count of transmitted data.