Data Register Allocation - Blocks 4, 5 Initial Setting Parameters (SHOT Action)

Block 4 (CH0) and block 5(CH1) parameters are shown in the table below. Before changing the parameters of
block 4 or 5, it is recommended that the control of the PID module be disabled.
Offset from the
Control
Register
CH0
CH1
+53
+130
Control Action
Heating/Cooling Control
+54
+131
(CH0 only)
External SP Input
+55
+132
(CH0 only)
+56
+133
Input Function
+57
Output Function (CH0)
+134
Output Function (CH1)
+58
+135
Input Type
Set Point (SP) Upper Limit/
+59
+136
Linear Conversion Maximum
Value
Set Point (SP) Lower Limit/
+60
+137
Linear Conversion Minimum
Value
+61
+138
Output ON/OFF Hysteresis
+62
+139
PV Correction
+63
+140
PV Filter Time Constant
+64
+141
Reserved
+65
+142
Alarm 1 Type
+66
+143
Alarm 2 Type
+67
+144
Alarm 3 Type
+68
+145
Alarm 4 Type
+69
+146
Alarm 5 Type
+70
+147
Alarm 6 Type
+71
+148
Alarm 7 Type
+72
+149
Alarm 8 Type
FC5A MicroSmart PID Module User's Manual FC9Y-B1283
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Parameter
0: Reverse control action (Heating)
1: Direct control action (Cooling)
0: Disable
1: Enable
0: Disabled
1: External SP input (4 to 20mA DC)
2: External SP input (0 to 20mA DC)
3: External SP input (1 to 5V DC)
4: External SP input (0 to 1V DC)
5: Cascade control
0: Input (CH0/CH1)
1: Difference input (CH0 - CH1)
2: Difference input (CH1 - CH0)
3: Addition input (CH0 + CH1)
0: Output (CH0)
1: Output (CH1)
2: Both outputs (CH0, CH1)
0: Output(CH1)
Output Function (CH0) has priority.
See 5-21 for the input types and range
When input is thermocouple or resistance thermometer:
Set point (SP) lower limit to input range upper limit
When input is voltage or current input:
Linear conversion minimum to input range upper limit
When input is thermocouple or resistance thermometer:
Input range lower limit to set point (SP) upper limit
When input is voltage or current input:
Input range lower limit to linear conversion maximum
When input range unit is Celsius:
0.1 to 100.0°C
When input range unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage or current input:
1 to 1000
When input range unit is Celsius:
-100.0 to 100.0°C
When input range unit is Fahrenheit:
-100.0 to 100.0°F
When input is voltage or current input:
-1000 to 1000
0.0 to 10.0 sec
0: No alarm action
1: Upper limit alarm
2: Lower limit alarm
3: Upper/Lower limits alarm
4: Upper/Lower limit range alarm
5: Process high alarm
6: Process low alarm
7: Upper limit alarm with standby
8: Lower limit alarm with standby
9: Upper/Lower limits alarm with standby
D
A
PID M
EVICE
LLOCATION OF
Description
ODULE
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
5-19