Examples - IDEC FC5A-F2M2 User Manual

Fc5a series microsmart pentra pid module
Table of Contents

Advertisement

7: A
PPLICATION
This chapter describes the PID modules application examples.
Application Example 1
This application example demonstrates the temperature control for a system using two electric furnaces. The
set point (SP) of CH0 control is 200°C. The set point (SP) of CH1 control is 210°C.
• PID control is performed based on the temperature input to the PID module. The control output is turned on
or off in accordance with the output manipulated variable (MV).
• PID parameters (proportional band/proportional gain, integral time, derivative time, and ARW) are
automatically calculated using auto-tuning (AT).
• If the process variable (PV) of CH0 control becomes 205°C or higher, the upper limit alarm output (Q0) is
turned on and the control is disabled.
• If the process variable (PV) of CH1 control becomes 215°C or higher, the upper limit alarm output (Q1) is
turned on and the control is disabled.
System Configuration and Wiring
Wiring Example of the FC5A-F2M2 [Non-contact voltage output (for SSR drive)/current output type]
+
SSR
-
Electric
Furnace 2
FC5A MicroSmart PID Module User's Manual FC9Y-B1283
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
E
XAMPLES
3-phase
Power Supply
Power
Supply
+
SSR
-
+
+
-
-
CH0 Thermocouple
Electric
Furnace 1
CH1 Thermocouple
A
PPLICATION
Terminal
Channel
No.
24V DC
Terminal
Channel
No.
IN0
OUT0
IN1
OUT1
PID Module (FC5A-F2M2)
E
XAMPLES
7-1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc5a-f2mr2