PID Module Configuration - Output Parameters Details

(1)
(2)
(3)
(4)
Output Parameters when Heating/Cooling Control is Enabled
(5)
(6)
(7)
Output parameters of CH0 control are described here. When the heating/cooling control is enabled, the control
period and the output manipulated variable (MV) upper and lower limits of CH1 are disabled. The parameters
(5) to (7) are enabled.
Output parameters for CH1 control are the same as those of CH0 control except the cooling control
parameters. However, the positions from the control register for each parameter differs. For details about the
positions from the control register of CH1 control, see 5-17 to 5-20
(1) Control Register+99: Output Type
Select the output type for the FC5A-F2M2. Voltage or current output can be selected.
Voltage output: 12V DC±15%
Current output: 4 to 20mA DC
FC5A MicroSmart PID Module User's Manual FC9Y-B1283