IDEC FC5A-F2M2 User Manual page 64

Fc5a series microsmart pentra pid module
Table of Contents

Advertisement

Program Parameters
Parameter
Set Point (SP)
Step Time
Wait Value
Proportional Term
Integral Time
Derivative Time
ARW (Anti-Reset Windup)
Output Manipulated Variable
Rate-of-Change
Alarm 1 Value
Alarm 2 Value
Alarm 3 Value
Alarm 4 Value
Alarm 5 Value
Alarm 6 Value
Alarm 7 Value
Alarm 8 Value
Reserved
Output Manipulated Variable
Upper Limit
Output Manipulated Variable
Lower Limit
Cooling Proportional Band
(CH0 only)
Overlap/Dead Band
(CH0 only)
FC5A MicroSmart PID Module User's Manual FC9Y-B1283
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
When input is thermocouple or resistance thermometer:
Set point (SP) lower limit to set point (SP) upper limit
When input is voltage or current input:
Linear conversion min. to linear conversion max.
When step time unit is Minute:
0 to 6000 minutes
When step time unit is Second:
0 to 6000 seconds
When input range unit is Celsius:
0 to 100°C
(Range with a decimal point: 0.0 to 100.0°C)
When input range unit is Fahrenheit:
0 to 100°F
(Range with a decimal point: 0.0 to 100.0°F)
When input is voltage or current input:
0 to 1000
Proportional band:
When input range unit is Celsius:
0 to 10000°C
(Range with a decimal point: 0.0 to 1000.0°C)
When input range unit is Fahrenheit:
0 to 10000°F
(Range with a decimal point: 0.0 to 1000.0°F)
When input is voltage or current input:
0.0 to 1000.0%
Proportional gain:
0.00 to 100.00%
0 to 10000 sec
0 to 10000 sec
0 to 100%
0 to 100%/sec
See 5-18 for the valid range of alarm 1 to alarm 8 values.
When output type is relay or voltage:
Output manipulated variable lower limit to 100%
When output type is current:
Output manipulated variable lower limit to 105%
When output type is relay or voltage:
0% to output manipulated variable upper limit
When output type is current:
-5% to output manipulated variable upper limit
0.0 to 10.0 times
(Cooling proportional band is the multiplication of heating proportional band)
When input range unit is Celsius:
-200.0 to 200.0°C
When input range unit is Fahrenheit:
-200.0 to 200.0°F
When input is voltage or current input:
-2000 to 2000
D
A
PID M
EVICE
LLOCATION OF
ODULE
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
5-23