Program Parameters
Parameter
Set Point (SP)
Step Time
Wait Value
Proportional Term
Integral Time
Derivative Time
ARW (Anti-Reset Windup)
Output Manipulated Variable
Rate-of-Change
Alarm 1 Value
Alarm 2 Value
Alarm 3 Value
Alarm 4 Value
Alarm 5 Value
Alarm 6 Value
Alarm 7 Value
Alarm 8 Value
Reserved
Output Manipulated Variable
Upper Limit
Output Manipulated Variable
Lower Limit
Cooling Proportional Band
(CH0 only)
Overlap/Dead Band
(CH0 only)
FC5A MicroSmart PID Module User's Manual FC9Y-B1283
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Description
When input is thermocouple or resistance thermometer:
Set point (SP) lower limit to set point (SP) upper limit
When input is voltage or current input:
Linear conversion min. to linear conversion max.
When step time unit is Minute:
0 to 6000 minutes
When step time unit is Second:
0 to 6000 seconds
When input range unit is Celsius:
0 to 100°C
(Range with a decimal point: 0.0 to 100.0°C)
When input range unit is Fahrenheit:
0 to 100°F
(Range with a decimal point: 0.0 to 100.0°F)
When input is voltage or current input:
0 to 1000
Proportional band:
When input range unit is Celsius:
0 to 10000°C
(Range with a decimal point: 0.0 to 1000.0°C)
When input range unit is Fahrenheit:
0 to 10000°F
(Range with a decimal point: 0.0 to 1000.0°F)
When input is voltage or current input:
0.0 to 1000.0%
Proportional gain:
0.00 to 100.00%
0 to 10000 sec
0 to 10000 sec
0 to 100%
0 to 100%/sec
See 5-18 for the valid range of alarm 1 to alarm 8 values.
When output type is relay or voltage:
Output manipulated variable lower limit to 100%
When output type is current:
Output manipulated variable lower limit to 105%
When output type is relay or voltage:
0% to output manipulated variable upper limit
When output type is current:
-5% to output manipulated variable upper limit
0.0 to 10.0 times
(Cooling proportional band is the multiplication of heating proportional band)
When input range unit is Celsius:
-200.0 to 200.0°C
When input range unit is Fahrenheit:
-200.0 to 200.0°F
When input is voltage or current input:
-2000 to 2000
D
A
PID M
EVICE
LLOCATION OF
ODULE
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
5-23