IDEC FC5A-F2M2 User Manual page 80

Fc5a series microsmart pentra pid module
Table of Contents

Advertisement

Offset from
the control
register
CH0
CH1
Output Manipulated
(14)
+32
+109
Variable Rate-of-Change
Output ON/OFF
(15)
+61
+138
Hysteresis
Manual Mode Output
(16)
+21
+24
Manipulated Variable
Loop Break Alarm (LA)
(17)
+35
+112
Time
Loop Break Alarm (LA)
(18)
+36
+113
Span
(19)
+95
Cooling Method
Cooling Proportional
(20)
+48
Band
Cooling Output ON/OFF
(21)
+98
Hysteresis
(22)
+50
Overlap/Dead Band
Program Control Mode
(23)
+91
+168
Start Type
Set Point (SP) when
(24)
+96
+173
Program Control Starts
(25)
+92
+169
Step Time Unit
(26)
+93
+170
Program End Action
(27)
+97
+174
Number of Repeats
FC5A MicroSmart PID Module User's Manual FC9Y-B1283
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
C
ONFIGURING
Parameter
0 to 100%/sec
When input range unit is Celsius:
0.1 to 100.0°C
When input range unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage or current:
1 to 1000
When heating/cooling control is disabled:
Output manipulated variable lower limit to output
manipulated variable upper limit
When heating/cooling control is enabled:
- Cooling output manipulated variable upper limit to
heating output manipulated variable upper limit
0 to 200 minutes
When input range unit is Celsius:
0 to 150 °C
(Range with a decimal point: 0.0 to 150.0°C)
When input range unit is Fahrenheit:
0 to 150 °F
(Range with a decimal point: 0.0 to 150.0°F)
When input is voltage or current:
0 to 1500
0: Air cooling
1: Oil cooling
2: Water cooling
0.0 to 10.0 times
(Cooling proportional band is the product of this value
and the heating proportional band)
When input range unit is Celsius:
0.1 to 100.0°C
When input range unit is Fahrenheit:
0.1 to 100.0°F
When input is voltage or current:
1 to 1000
When input range unit is Celsius:
-200.0 to 200.0°C
When input range unit is Fahrenheit:
-200.0 to 200.0°F
When input is voltage or current:
-2000 to 2000
0: PV start
1: PVR start
2: SP start
When input is thermocouple/resistance thermometer:
Set point (SP) lower limit to set point (SP) upper limit
When input is voltage or current:
Linear conversion min. to linear conversion max.
0: Minute
1: Second
0: Terminate program control
1: Continue program control (Repeat)
2: Hold program control
0 to 10000 times
PID M
W
ODULE USING
Setting Range
LDR
IND
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
6-15