(6) Control Register+65: Alarm 1 Type
Control Register+66: Alarm 2 Type
Control Register+67: Alarm 3 Type
Control Register+68: Alarm 4 Type
Control Register+69: Alarm 5 Type
Control Register+70: Alarm 6 Type
Control Register+71: Alarm 7 Type
Control Register+72: Alarm 8 Type
Select one of the alarm types from upper limit alarm, lower limit alarm, upper/lower limits alarm, upper/lower
limit range alarm, process high alarm, process low alarm, upper limit alarm with standby, lower limit alarm with
standby, upper/lower limits alarm with standby, and no alarm action. The same alarm type can be selected in
multiple alarms.
Alarm Actions
ON
OFF
-Alarm Value
[Setting Example]
Set Point (SP)
Alarm 1 Value
Alarm 1 Hysteresis
[Alarm Action]
205
C
Process Variable (PV)
ON
OFF
Upper/Lower Limits Alarm
ON
OFF
Alarm Value
[Setting Example]
Set Point (SP)
Alarm 1 Value
Alarm 1 Hysteresis
[Alarm Action]
205
C
Process Variable (PV)
197 C
Process Variable (PV) 203
ON
OFF
6-26
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
W
LDR
IND
Upper Limit Alarm
Alarm Hysteresis
SP
+Alarm Value
: 200 C
: 5 C
: 2.0
C
Process Variable (PV): Alarm Output ON
203
C
: Alarm Output OFF
5
C
2.0
C
200
203
205
C
C
C
Alarm Hysteresis
SP
Alarm Value
: 200 C
: 5 C
: 2.0
C
Process Variable (PV) or
195
C
: Alarm Output ON
C
: Alarm
Output OFF
5 C
5 C
2.0 C
2.0 C
195
200
C
197
C
C
203
C
205
C
FC5A MicroSmart PID Module User's Manual FC9Y-B1283
Lower Limit Alarm
Alarm Hysteresis
ON
OFF
-Alarm Value
SP
+Alarm Value
[Setting Example]
Set Point (SP)
: 200 C
Alarm 1 Value
: -5 C
Alarm 1 Hysteresis
: 2.0
C
[Alarm Action]
Process Variable (PV)
195
: Alarm Output ON
C
197
C
Process Variable (PV) : Alarm Output OFF
-5
C
2
C
ON
OFF
195
197
200
C
C
C
Upper/Lower Limit Range Alarm
Alarm Hysteresis
ON
OFF
Alarm Value
SP
Alarm Value
[Setting Example]
Set Point (SP)
: 200 C
Alarm 1 Value
: 5 C
Alarm 1 Hysteresis
: 2.0
C
[Alarm Action]
195
C
Process Variable (PV)
205
C
: Alarm
Output ON
207 C
Process Variable (PV) or
Process Variable (PV)
193
C
: Alarm Output OFF
5 C
5 C
2.0 C
2.0 C
ON
OFF
193
195
200
C
205
C
C
C
207
C