Factory Default Settings Of The Pid Module - IDEC FC5A-F2M2 User Manual

Fc5a series microsmart pentra pid module
Table of Contents

Advertisement

Factory Default Settings of the PID Module

The factory default settings of the parameters of each block are described. Values indicated in
parentheses are stored in the data registers allocated to each block.
Block 1 Write Only Parameters
Offset from
the Control
Register
CH0
CH1
+20
+23
Set Point (SP)
+21
+24
Manual Mode Output Manipulated Variable
+22
+25
Operation Parameter *1
*1: For details about the operation parameter, see page 5-10.
Blocks 2, 3 Basic Parameters
Offset from
the Control
Register
CH0
CH1
+26
+103 Proportional Term
+27
+104 Integral Time
+28
+105 Derivative Time
+29
+106 ARW (Anti-Reset Windup)
+30
+107 Control Period
+31
+108 Reset
+32
+109 Output Manipulated Variable Rate-of-Change 0%/second (0)
+33
+110 Set Point (SP) Rise Rate
+34
+111 Set Point (SP) Fall Rate
+35
+112 Loop Break Alarm (LA) Time
+36
+113 Loop Break Alarm (LA) Span
+37
+114 Alarm 1 Value
+38
+115 Alarm 2 Value
+39
+116 Alarm 3 Value
+40
+117 Alarm 4 Value
+41
+118 Alarm 5 Value
+42
+119 Alarm 6 Value
+43
+120 Alarm 7 Value
+44
+121 Alarm 8 Value
+45
+122 Reserved
+46
+123 Output Manipulated Variable Upper Limit
+47
+124 Output Manipulated Variable Lower Limit
+48
+125 Cooling Proportional Band (CH0 only)
+49
+126 Cooling Control Period (CH0 only)
+50
+127 Overlap/Dead Band (CH0 only)
Cooling Output Manipulated Variable Upper
+51
+128
Limit (CH0 only)
Cooling Output Manipulated Variable Lower
+52
+129
Limit (CH0 only)
FC5A MicroSmart PID Module User's Manual FC9Y-B1283
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Parameter
0°C (0)
0% (0)
0
Parameter
Proportional band: 10°C (10)
200 sec (200)
50 sec (50)
50% (50)
FC5A-F2MR2 (Relay output): 30 sec (30)
FC5A-F2M2 (Non-contact voltage output):
0.0°C (0)
0°C/minute (0)
0°C/minute (0)
0 minutes (0)
0°C (0)
0°C (0)
0
100% (100)
0% (0)
[CH0] 1.0 times (10)
[CH1] 0
[CH0]
FC5A-F2MR2 (Relay output): 30 sec (30)
FC5A-F2M2 (Non-contact voltage
[CH1] 0
[CH0] 0.0°C (0)
[CH1] 0
[CH0] 100% (100)
[CH1] 0
[CH0] 0% (0)
[CH1] 0
A
PPENDIX
Default Value
Default Value
3 sec (3)
output): 3 sec (3)
9-9