PID Module Parameter Configuration
The parameters of the PID module can be configured in the Expansion Modules Configuration and PID
Module Configuration dialog boxes. The procedure to configure the PID module is described below.
Parameter Configuration Example
Quantity of Modules: 1 unit
Slot No.:
Module Type No.:
Data Register:
Internal Relay:
I/O Function:
Input
Output
Alarm 1 Type
Alarm 1 Value
Set Point (SP)
Control Action
AT Bias
Parameter Configuration Procedure
1. Expansion Modules Configuration
Select Configuration > Expansion Modules from the WindLDR menu bar to open the Expansion
Modules Configuration dialog box.
In the Expansion Modules Configuration dialog, configure the quantity of modules, slot number, module
type No., control register (data register) and control relay (internal relay). Click on Configure
Parameters button to open the PID Module Configuration dialog box
Expansion Modules Configuration Dialog Box
(1)
(2)
(3)
(4)
(5)
(1)
Quantity of Modules
(2)
Slot No.
(3)
Module Type No.
(4)
Data Register
(5)
Internal Relay
7-16
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Slot 1
FC5A-F2M2
D1000
M1000
Used as a heating/cooling control PID module
CH0
Type K thermocouple with a decimal point
0.0 to 400.0
(
)°C
Non-contact voltage output (for SSR drive)
Upper/Lower limits alarm with standby
5.5°C
200.0°C
PID control action [P, I, D, and ARW are
automatically calculated using auto-tuning
(AT).]
20.0°C
Item
1
Slot 1
FC5A-F2M2
D1000
M1000
FC5A MicroSmart PID Module User's Manual FC9Y-B1283
CH1
Non-contact voltage output (for SSR drive)
Setting