Data Register Allocation - Blocks 2, 3 Basic Parameters (SHOT Action)

Block 2 (CH0) and block 3 (CH1) parameters are shown in the table below. The parameters of block 2 and 3
can be changed while the control of the PID module is enabled.
Offset from the
Control
Register
CH0
CH1
+26
+103
Proportional Term
+27
+104
Integral Time
+28
+105
Derivative Time
+29
+106
ARW (Anti-Reset Windup)
+30
+107
Control Period
+31
+108
Reset
Output Manipulated Variable
+32
+109
Rate-of-Change
+33
+110
Set Point (SP) Rise Rate
+34
+111
Set Point (SP) Fall Rate
+35
+112
Loop Break Alarm (LA) Time
+36
+113
Loop Break Alarm (LA) Span
+37
+114
Alarm 1 Value
+38
+115
Alarm 2 Value
+39
+116
Alarm 3 Value
+40
+117
Alarm 4 Value
+41
+118
Alarm 5 Value
+42
+119
Alarm 6 Value
+43
+120
Alarm 7 Value
+44
+121
Alarm 8 Value
+45
+122
Reserved
FC5A MicroSmart PID Module User's Manual FC9Y-B1283
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Parameter
Proportional band:
When input range unit is Celsius:
0 to 10000°C
(Range with a decimal point: 0.0 to 1000.0°C)
When input range unit is Fahrenheit:
0 to 10000°F
(Range with a decimal point: 0.0 to 1000.0°F)
When input is voltage or current input:
0.0 to 1000.0%
Proportional gain:
0.00 to 100.00%
0 to 10000 sec
0 to 10000 sec
0 to 100%
1 to 120 sec
When input range unit is Celsius:
-100.0 to 100.0 °C
When input range unit is Fahrenheit:
-100.0 to 100.0 °F
When input is voltage or current input:
-1000 to 1000
0 to 100%/sec
When input range unit is Celsius:
0 to 10000°C/min
(Range with a decimal point: 0.0 to 1000.0°C/min)
When input range unit is Fahrenheit:
0 to 10000°F/min
(Range with a decimal point: 0.0 to 1000.0°F/min)
When input is voltage or current input:
0 to 10000/min
When input range unit is Celsius:
0 to 10000°C/min
(Range with a decimal point: 0.0 to 1000.0°C/min)
When input range unit is Fahrenheit:
0 to 10000°F/min
(Range with a decimal point: 0.0 to 1000.0°F/min)
When input is voltage or current input:
0 to 10000/min
0 to 200 minutes
When input range unit is Celsius:
0 to 150 °C
(Range with a decimal point: 0.0 to 150.0°C)
When input range unit is Fahrenheit:
0 to 150 °F
(Range with a decimal point: 0.0 to 150.0°F)
When input is voltage or current input:
0 to 1500
See 5-18 for the valid range of alarm 1 to alarm 8 values.
D
A
PID M
EVICE
LLOCATION OF
Description
ODULE
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
5-17