IDEC FC5A-F2M2 User Manual page 106

Fc5a series microsmart pentra pid module
Table of Contents

Advertisement

(23) Control Register+91: Program Control Mode Start Type
Select the program control mode start type from the following:
When the program control is started, the time is advanced until the set point (SP) becomes
PV Start
equal to the process variable (PV), and then the program control starts.
When "Continue program control (Repeat)" is selected as the program end action, the time is
PVR Start
advanced until the set point (SP) becomes equal to the process variable (PV) at which
program control is terminated, and then the next program control starts.
When the program control is started, the program control starts from the set point (SP) that is
SP Start
configured as "Set Point (SP) when Program Control Starts."
Examples for the PV start, PVR start and SP start actions are described using the following program pattern.
Step Number
0
Set Point (SP)
150°C
100°C
50°C
60 min
PV Start Action [Process variable (PV) is 25°C]
Step Number
0
Set Point (SP)
150°C
100°C
50°C
25°C
15 min
45
min
Program Control Run
FC5A MicroSmart PID Module User's Manual FC9Y-B1283
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
C
ONFIGURING
1
2
3
4
60 min
60 min
30
30
min
min
1
2
3
4
60 min
30
30
60 min
min
min
When the program control is started, the time will be
advanced (shown in dotted line) until the set point (SP)
becomes equal to 25°C of the process variable (PV),
and then the program control will start from this point.
PID M
W
ODULE USING
IND
Time
Time
LDR
6-41