IDEC FC5A-F2M2 User Manual page 59

Fc5a series microsmart pentra pid module
Table of Contents

Advertisement

D
A
PID M
EVICE
LLOCATION OF
Output Manipulated Variable
+46
+123
Upper Limit
Output Manipulated Variable
+47
+124
Lower Limit
Cooling Proportional Band
+48
+125
(CH0 only)
Cooling Control Period
+49
+126
(CH0 only)
Overlap/Dead Band
+50
+127
(CH0 only)
Cooling Output Manipulated
+51
+128
Variable Upper Limit
(CH0 only)
Cooling Output Manipulated
+52
+129
Variable Lower Limit
(CH0 only)
Valid Range for Alarm 1 to Alarm 8 Settings
Alarm Type
Upper Limit Alarm
Lower Limit Alarm
Upper/Lower Limits Alarm
Upper/Lower Limit Range Alarm
Process High Alarm
Process Low Alarm
Upper Limit Alarm with Standby
Lower Limit Alarm with Standby
Upper/Lower Limits Alarm with Standby
*1: When input is voltage/current, full scale is the linear conversion span.
*2: When input is voltage/current, the valid range is the linear conversion minimum value to linear conversion
maximum value.
5-18
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
ODULE
When output type is relay or voltage:
Output manipulated variable lower limit to 100%
When output type is current:
Output manipulated variable lower limit to 105%
When output type is relay or voltage:
0% to output manipulated variable upper limit
When output type is current:
-5% to output manipulated variable upper limit
0.0 to 10.0 times
(Cooling proportional band is the multiplication of heating
proportional band)
1 to 120 sec
When input range unit is Celsius:
-200.0 to 200.0°C
When input range unit is Fahrenheit:
-200.0 to 200.0°F
When input is voltage or current input:
-2000 to 2000
When output type is relay or voltage:
Cooling output manipulated variable lower limit to 100%
When output type is current:
Cooling output manipulated variable lower limit to 105%
When output type is relay or voltage:
0% to cooling output manipulated variable upper limit
When output type is current:
-5% to cooling output manipulated variable upper limit
–(Full scale) to full scale *1
–(Full scale) to full scale *1
Input range lower limit to input range upper limit *2
Input range lower limit to input range upper limit *2
–(Full scale) to full scale *1
–(Full scale) to full scale *1
FC5A MicroSmart PID Module User's Manual FC9Y-B1283
Valid Range
0 to full scale *1
0 to full scale *1
0 to full scale *1
R/W
R/W
R/W
R/W
R/W
R/W
R/W