6.3.26 BA Part Set & BA Entry/Exit Full Set
Instant B.A P. Set &_B.A
E/Ex F. Set
DE, UK
All other country versions

6.3.27 BA Entry/Exit Full Set

Burglar Alarm Full set
Entry/Exit
DE, UK
All other country versions
30
Siemens Building Technologies
Fire Safety & Security Products
Brief description: BA external delay; Internal (Reverse function to Input 29)
On part set: Direct triggering in the assigned partition.
On full set: Delayed entry and exit triggering in the assigned partition.
If the input remains triggered up the end of the delay time, the partition is again unset.
If the input remains triggered up the end of the delay time, the partition remains full set and an alarm is
triggered.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
7
External bell
7
Strobe light
7
Alarm in memory
X
X
Block lock not released
5
Buzzer
7
Burglar alarm system transmission line
7
Burglar alarm partition transmission line
7
Transmission line input
Partition parameters:
X =
Triggering regardless of the partition mode.
5 =
Triggering only if "Buzzer On" in the keypad parameter is chosen.
7 =
Triggering only after delay.
Brief description: BA external delay; Internal inactive
On part set: No triggering in the assigned partition.
On full set: Delayed entry and exit triggering in the assigned partition.
If the input remains triggered up the end of the delay time, the partition is again unset.
If the input remains triggered up the end of the delay time, the partition remains full set and an alarm is
triggered.
Partition mode:
Unset
Part set
Full set
Effects on the following outputs when the below partition parameters are preset:
7
External bell
7
Strobe light
7
Alarm in memory
X
X
Block lock not released
5
Buzzer
7
Burglar alarm system transmission line
7
Burglar alarm partition transmission line
7
Transmission line input
Partition parameters:
X =
Triggering regardless of the partition mode.
5 =
Triggering only if "Buzzer On" in the keypad parameter is chosen.
7 =
Triggering only after delay.
07.2009