6.3.14 External Line Fault

External
Acts exactly the same as an internal line fault. Must be used for external communicators so that the parameters which react on
Line Fault
a line fault also function with external communicators. In contrast to an internal line fault, this fault remains triggered until the
input is again in the normal state.
Input triggered
Partition mode:
Unset
Part set
Full set
6
6
6
X
X
3
3
X
Partition parameters:
X =
Triggering regardless of the partition mode.
3 =
Triggering only if "transmission" parameter is chosen.
6 =
Triggering only if "Forced Set" parameter ->"Not Allowed" is chosen.

6.3.15 Battery Supervision (SI120 only)

Battery Supervision
Low battery is detected below 11.6 V. End of low battery is generated above 12 V. Lost of battery is also
detected.
(SI120 only)
Using additional hardware SMX23/26/29 (approvals), battery is tested every 60 seconds.
Use output 'Supervision Batterie' only for triggering SMX23/26/29.
Siemens Building Technologies
Fire Safety & Security Products
line fault
Effects on the following outputs when the below partition parameters are preset:
Cannot full set
Cannot part set
Block lock output not enabled
Line monitoring of transmission line