ARC

13
ARC
This menu function enables the following parameters:
[TM61] ARC 1 /
[TM62] ARC 2
13.1

ARC2 Backup ARC1

Backup transmission
This parameter defines whether the event is to be transmitted to Receiver 2 (emergency telephone station 2)
as increased security in the event of an unsuccessful transmission to Receiver 1 (emergency telephone
station 1). This applies only for Receiver 1 to Receiver 2 but not the other way round.
13.2

Serial Port Protocol (ARC1)

72
Siemens Building Technologies
Fire Safety & Security Products
ARC Alarm Receiver Central or CMS Control Management Station is used to follow
up an intervention by a security provider or the police.
Serial protocol
Three telephone numbers
Transmission protocol
Customer number per main partition
Code for alarm verification
Audio verification
Automatic test call
NOTE
The offset for the start of the automatic test call is to be entered in the "Offset test call 1 Tele-
com options" (TM671) in the engineer menu.
Serial Transmission uses SMN42/SMN43 Module only (SI120). Additonnaly
SML2465 can be used (SI220).
During the upgrade from A7 to A8 the parameter serial transmission is switched
off.
SMN42/SMN43 is connected to the control unit but not to the network. Initialization
and local access are set to transmission. If you try to access via the keypad, the
message "transmission on going" will be displayed. Access will be granted after
2'30".
Callback to a free number: if the control panel does not call the Sylcom station
which initiated the callback but another Sylcom station, the error message which
will be displayed has to be ignored.
07.2009