W2 Link Unit Setting Dialog Box - Panasonic FP7 User Manual

Multi-wire link unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

MEWNET-W2

5.3.5 W2 Link Unit Setting dialog box

 Setting item
No.
Item
Use PLC link
Unit No.:
Link relay area
holding start
number
Link register area
holding start
number
Link data refresh
unit
5-8
Range
For using the PLC link, check the checkbox.
Specify a unit number for the own unit. When setting it using a user
program (PMSET/pPMSET instruction), specify "0". The unit
number selector on the front panel of the unit needs to be set to
00.
Set the starting word number of a device used as hold type. The
holding start number is specified as a relative value from the
beginning of "Relay Link Area" and "Data Link Area".
For link relays: 0-256
For link registers: 0 to 4096
Example 1) When specifying 0, the area in the selected range is
hold type.
Example 2) When specifying the maximum value, the area in the
selected range is non-hold type.
Specify the unit to refresh the I/O by the PLC link in the format of
(set value x 256 bytes/scan). By default, all points are refreshed
collectively when specifying 0. Although the responsiveness is
improved, the scan time of a single unit becomes longer. When a
set value is changed, data of the set number of bytes is refreshed
for each scan. Although the responsiveness is deteriorated, the
scan time of a single unit becomes shorter.
Remarks