Panasonic FP7 User Manual page 125

Multi-wire link unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

 [D]: Processing result
• The execution result is stored in the area of one word.
• The execution result code in the lower byte is valid when the processing flag of bit 15 is zero.
bit no. 15
Processing flag
0: Processing completed
1: Processing in progress
Execution result flag
0: Normal end
1: Abnormal end
 Precautions during programming
• The unit number of the FP7 MW Unit can be set by PMSET/pPMSET instruction only when
the unit number selector on the unit is set to 0.
• Describe UNITSEL instruction immediately before PMSET/pPMSET instruction and specify
the slot number of the unit which acquires parameters in [S1] and 0 in [S2].
• Confirm the execution result when the bit 15 (processing flag) in the area specified in [D]
changes from 1 to 0.
• The content set by PMSET/pPMSET instruction is not held in case of power outage. Turn on
the power supply again and switch to RUN mode to return to the configuration information
set in the tool software.
• When setting it for the FP7 MW Unit, it cannot be used in an interrupt program.
REFERENCE
For details of sample programs of "PMGET" and "pPMSET" instructions,
refer to "9.1.7 PMSET/pPMSET instruction (For MEWNET-W2)".
8 7
0 0 0 0 0 0
Execution result code
0: Normal end
1: Communication port specified by UNITSEL instruction
is incorrect.
2: Setting error
3: Mode change error
4: Communication port being used
5: Change request parameter mismatch (Parameters
specified by operand are different when the setting
process starts and ends.)
7: When the unit number selector on the MW Unit is not 0.
9.1 Communication Instructions
0
9-13