MEWNET-W

4.3.6 Configuration Using User Programs

In MEWNET-W, unit numbers, link relays and link registers can be allocated by the user
programs (PMSET/pPMSET instruction). The unit number selector on the front panel of the
unit needs to be set to 00.
 Sample program
This sample program shows the allocation of unit number, link relay and link register for the
FP7 MW Unit (W Link Unit) installed in the slot number 1.
R100
R101
4-10
MV.US
MV.US
MV.US
MV.US
MV.US
MV.US
MV.US
MV.US
MV.US
MV.US
UNITSEL
pPMSET
DT0
S1
U10
DT100
S
D
U50
DT101
S
D
U100
DT102
S
D
U0
DT103
S
D
U64
DT104
S
D
U128
DT105
S
D
U10
DT106
S
D
U20
DT107
S
D
U40
DT108
S
D
U40
DT109
S
D
Communication port settings
U1
U0
S1: Slot no. (U1)
S2: Port no. (U0)
S1
S2
MW communication parameter settings
U10
DT100
S1: Communication parameter
n
D1
D1: Processing result storage
PLC link parameter settings
DT100: Unit no. (U10)
DT101: Link relay holding start
relative address (U50)
DT102: Link register holding
start relative address (U100)
DT103: Memory block no.
(WL0-63,LD=0-127) (U0)
DT104: Link relay range (U64)
DT105: Link register range
(U128)
DT106: Link relay transmission
start no. (U10)
DT107: Link relay transmission
size (U20)
DT108: Link register transmission
start no. (U40)
DT109: Link register transmission
size (U40)
setting area (DT0)
n: No. of set words (U10)
destination (DT100)