9.1.6 PMSET/pPMSET Instruction (For MEWNET-W)

Unit numbers and PLC link allocation can be set.
 Instruction format
R100
(Note): The above figure shows the case that the FP7 MW Unit of S1=U1 (slot no.1) is specified by UNITSEL
instruction.
 Operand
Item
Settings
Specify the starting address of the device storing
S
set communication parameters.
n
Specify the number of set words.
Specify the device area of the local unit storing the
D
processing result (1 word).
(Note 1): When the unit number is 17 or more, specify 1.
 [S] to [S+9]: Communication parameter settings in W mode
Parameter
[S]
Unit no.
[S+1]
Link relay holding start no.
Link register holding start
[S+2]
no.
[S+3]
Memory block number
[S+4]
Range of link relays
[S+5]
Range of link registers
Starting number for link
[S+6]
relay transmission
Link relay transmission
[S+7]
size
Starting number for link
[S+8]
register transmission
Link register transmission
[S+9]
size
9-12
UNITSEL
PMSET
DT0
S
Range
Description
It can be changed only when the rotary switch on the
U1 to U32
front panel of the unit is set to 0. When using the PLC
link, set it in the range of 1 to 16.
U0 to U128
Specify the hold area of link relays by word numbers.
U0 to U128
Specify the hold area of link relays by word numbers.
U0 to U7
Memory block no. of PLC link area
U0 to U64
Link relay usable range in the above memory block
U0 to U128
Link register usable range in the above memory block
U0 to U63
Link relay transmission start no.
U0 to U64
Link relay transmission size
U0 to U128
Link register transmission start no.
As for the link register transmission size, up to 127 words
U1 - U12
can be sent.
U1
U0
S1
S2
U1
DT100
n
D
Settable device
WX,WY,WR,WL,DT,LD
WX,WY,WR,WL,DT,LD,U
WX,WY,WR,WL,DT,LD
Setting range
10 or 1 (Note 1)