Panasonic FP7 User Manual page 17

Multi-wire link unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

 Specifications
Item
Communication
method
Transmission system
Transmission line
Transmission
distance (Note 1)
Baud rate
No. of slave units
No. of control I/O
points (Note 2)
Interface
Transmission error
check
(Note1): The transmission distance varies according to the used cable and unit.
(Note 2): The number of I/O points that can be actually controlled varies according to the configuration..
 Example of application
The remote I/O control can be performed by connecting slave units compliant with Panasonic
MEWNET-F.
• FP I/O terminal board
• FP I/O terminal unit
(Note): It cannot be connected to FP2 Slave Unit or FP3 Slave Unit (discontinued products).
Specifications
Polling
Baseband
Twisted pair cable / VCTF cable
Max. 700 m (when using twisted pair cable)
Max. 400 m (when using VCTF cable)
500 kbps
Max. 32 units (Per master unit)
Max. 4,096 units (Per master unit)
Conforming to RS-485
CRC method
1.2 Network Type
1-7