Advertisement

5.2 Setting the Switches of the Unit

For using the FP7 MW Unit as W2 link unit, the switches on the front of the unit need to be set.
 Mode setting switch
Each mode is set with the four dip switches on the front of the unit.
1
2
3
4
ON OFF
No.
Item
Operation
1
mode
2
Mode
3
4
Baud rate
(Note 1): All the switches are set to OFF at the factory.
(Note 2): Be sure the power is off when changing the switches.
 Unit number selector
Specify the own unit number by the two rotary switches on the front of the unit.
UNIT
NO.
Range
Description
01 to 32
For target unit of PLC link
01 to 64
For the data transfer target units (Note 1)
When setting it in the configuration of the tool software or user program (PMSET/pPMSET
00
instruction).
(Note 1): It indicates the range that can be specified. The range of units that can be actually connected is up to 32
units.
(Note 2): Be sure the power is off when changing the switches.
Range
OFF: Non-PLC link mode, ON: PLC link mode
Set 2 to ON and 3 to OFF. The unit operates as the unit for "MEWNET-W2".
For "MEWNET-W2", set it to OFF for 500 kbps and ON for 250 kbps.