Elements which compose command responses
Number
Name
①
Header
②
Address
③
Identification code
④
Command code
⑤
0 (Fixed)
⑥
Depth
⑦
Relay source unit no.
⑧
Relay destination slot no.
⑨
Response code
⑩
Error code
⑪
Check code
⑫
Terminator
Description
% or <
"EE" (Fixed): Specify the own unit.
"#": Indicates a command.
"$": Indicates a normal response.
"!": Indicates an error response.
"LC": Indicates the hierarchy control command.
"0" x 8 characters of LC command are given.
"00" to "01": Specify the depth to a connected unit. For the FP7 MW
Unit, up to the depth 1 can be specified.
"01" to "32": Specify a relay source unit number.
"0x01" to "0x10": For the FP7 MW Unit, specify slot numbers.
Specify slot numbers (01 to 16) converted to hexadecimal.
"LC": It is returned for a normal response.
An error code is returned when an error occurs.
BCC code is stored.
"CR" (0D:Hex):
7.4 Relevant Information