Specifications
10.1 Specifications
10.1.1 General Specifications
Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Vibration resistance
Shock resistance
Noise resistance
Environment
EU Directive
applicable standard
Overvoltage category
Pollution degree
Weight (main unit)
Consumption current
10.1.2 Performance Specifications
Transmission specifications
Item
Communication method
Transmission system
Baud rate
Transmission distance
(Total length)
No. of connected units
Transmission error check
Synchronous method
Interface
Transmission line
RAS function
(Note): For details of the specifications of applicable cables, refer to "3.1.1 Applicable cables".
10-2
Specifications
0 °C to 55 °C
-40 °C to +70 °C
10 to 95 %RH (at 25 °C, non-condensing)
10 to 95 %RH (at 25 °C, non-condensing)
10 to 55Hz, 1 cycle/min.
(Double amplitude of 0.75 mm, 10 min. on 3 axes)
2
98m/s
, 4 times on X, Y and Z directions
1,000 V[P-P] with pulse widths 50 ns / 1µs (based on in-house measurements)
Free from corrosive gases and excessive dust.
EMC Directive: EN61131-2
Category II
Pollution level 2
Approx. 100 g
100mA or less
W mode
Token bus
Baseband
500k bit/s
Max. 800m
Max. 32 units
CRC (Cyclic Redundancy Check) method
Start stop synchronous system
Conforming to RS-485
Twisted pair cable
Hardware self-diagnosis function
Specifications
W2 mode
500k bit/s、250k bit/s
Max. 800m (500k bit/s)
Max. 1200m (250k bit/s)
F mode
Polling
500k bit/s
Max. 700m
Master unit: 1 unit + Slave
units: Max. 32 units
Twisted pair, VCTF