3.2 Optional Allocation Using FPWIN GR7
The registered unit and the starting word number are included in the I/O map. A number
that combines the starting word number registered for each unit and 0 to F becomes the
starting I/O number.
7.
Repeat registrations.
8.
Press the [OK] button while the "FP7 configuration" dialog box is displayed.
● The I/O map registered using FPWIN GR7 is downloaded into the CPU unit, together with
other project information. If a difference with the actual units and/or attachment status is
identified when power supply is turned on or during operation, such a difference is reported
as a self-diagnosis error.
● If a starting word number is not entered, the system automatically enters one.
● Based on the starting word number allocated to each unit, I/O numbers are allocated.
● The starting number of I/O numbers allocated to the internal functions of the CPU unit can
be changed to another number from the word number 0.

3.2.2 Optional Settings in the "Unit Selection" Dialog Box

Input time constants
● Input time constants for an input unit or a mixed input/output unit can be changed as
necessary. Select, and set for each unit, a desirable value from "No settings", 0.1, 0.5, 1.0,
5.0, 10.0, 20.0 or 70.0 ms. The selected time constants are added to the hardware-specific
response time of each unit.
● For details, please see the FP7 Digital Input/Output Unit Users Manual.
Exclude this unit from the scope of verification.
● In general, this check box should be turned off.
● If you want to exclude this unit from the scope of verification error temporarily for unit
replacement or adjustment, turn on this check box.
Exclude this unit from the scope of I/O refresh.
● In general, this check box should be turned off. Input/output processing is performed at the
timing of I/O refresh in a normal scan.
● By using operation devices "Direct input IN" or "Direct output OT", it becomes possible to
directly perform input/output processing during operation, independent of normal I/O refresh.
When this operation device is used, turn on the check box [Exclude this unit from the scope
of I/O refresh].
● By turning this check box on, all inputs and outputs of registered units are excluded from the
scope of I/O refresh.

3.2.3 Settings When Using Expansion Unit

Make the settings according to the used configuration.
3-8
WUME-FP7CPUH-09