Temperature requirements for the HPE ProLiant XL170r
Gen10 Server
To ensure continued safe and reliable equipment operation, install or position the rack in a well-ventilated,
climate-controlled environment.
The operating temperature inside the rack is always higher than the room temperature and is dependent
on the configuration of equipment in the rack. Check the TMRA for each piece of equipment before
installation.
CAUTION: To reduce the risk of damage to the equipment when installing third-party options:
Do not permit optional equipment to impede airflow around the server or to increase the internal
rack temperature beyond the maximum allowable limits.
Do not exceed the manufacturer's TMRA.
Thermal limitations for different options installed in the servers may differ depending on the chassis
configuration. For more information about product features, specifications, options, configurations, and
compatibility, see the product QuickSpecs on the Hewlett Packard Enterprise website (http://
www.hpe.com/info/qs).
Determine if there are temperature requirements for the component. For more information, see List of
components with temperature requirements in the HPE ProLiant XL170r Gen10 Server.
If necessary, populate drive bays in the chassis with drive blanks. For more information, see Drive blank
installation guidelines for the HPE ProLiant XL170r Gen10 Server.
List of components with temperature requirements in the HPE ProLiant
XL170r Gen10 Server
The maximum inlet ambient temperature for most components installed in the server is 35°C (95°F).
Some components, however, are subject to thermal limitations depending on the chassis model and the
fan configuration. If two or more components with temperature requirements are installed in the server,
observe the lowest maximum inlet ambient temperature.
Processors
Description
Processor with a
TDP (thermal
design power) of
125 W or greater
1
If the component is installed in server 1 or server 2, and the server is installed in the Apollo r2200 Gen10 Chassis,
drive blanks must be installed in drive bays 1-2 and 2-2. Similarly, if the component is installed in server 3 or server 4,
and the server is installed in the Apollo r2200 Gen10 Chassis, drive blanks must be installed in drive bays 3-2 and
4-2. For more information, see Drive blank installation guidelines for the HPE ProLiant XL170r Gen10 Server.
90

Temperature requirements for the HPE ProLiant XL170r Gen10 Server

Chassis
Number of LFF drives that
correspond to the server
Apollo r2200
3 drives
Gen10 Chassis
Apollo r2200
0 to 2 drives
Gen10 Chassis
Maximum inlet ambient
temperature
30°C (86°F)
1
35°C (95°F)