YASKAWA PROFINET V1000 Technical Manual page 29

Yaskawa ac drive-v1000 option
Hide thumbs Also See for PROFINET V1000:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
F7-27
Dynamic Output Assembly
(3FF)
Parameter 5
<10>
F7-33
Dynamic Input Assembly
(405)
Parameter 1
<10>
F7-34
Dynamic Input Assembly
(406)
Parameter 2
<10>
F7-35
Dynamic Input Assembly
(407)
Parameter 3
<10>
F7-36
Dynamic Input Assembly
(408)
Parameter 4
<10>
F7-37
Dynamic Input Assembly
(409)
Parameter 5
<10>
H5-11
Communications ENTER Function
(43C)
Selection
<1> Set b1-02 = 3 to start and stop the drive with the PROFINET master device using serial communications.
Set b1-01 = 3 to control the frequency reference of the drive via the master device.
<2> Setting this parameter to 3 will cause the drive to continue operation after detecting a fault. Take proper measures such as installing an
emergency stop switch when using setting 3.
<3> Available in the V1000 software versions PRG: 1024 and later. Refer to the instruction manual of a specific drive to determine if settings 4 and
5 are available in the drive.
<4> Cycle power for setting changes to take effect.
<5> If F7-13 is set to 0, then all IP Addresses (F7-01 to F7-04) must be unique.
<6> Set F7-01 to F7-12 when F7-13 is set to 0.
<7> Default setting differs by drive software version.
1012 to 1015: 0
≥1016: 1
<8> Set F7-15 when F7-14 is set to 0 or 2.
<9> The setting values differ by drive software version.
1012 to 1015
Default: 0
Range: 0, 10, 100
≥1016
Default: 10
Range: 10, 100
<10> If a value other than 0 is assigned to parameters F7-23 to F7-27 and F7-33 to F7-37 by the drive, that value will take precedent over a value set
by the configuration software. If the value in the drive is 0 (default), the value from the configuration software is used.
YASKAWA ELECTRIC SIEP C730600 70B V1000 Option SI-EP3/V Technical Manual
Sets configurable output 5.
Sets configurable input 1.
Sets configurable input 2.
Sets configurable input 3.
Sets configurable input 4.
Sets configurable input 5.
Selects whether an Enter command is necessary to change parameter
values via MEMOBUS/Modbus communications.
0: Parameter changes are activated when ENTER command is written
1: Parameter changes are activated immediately without use of ENTER
command
6 Related Drive Parameters
Description
Values
Default: 0H
Min.: 0H
Max.: FFFFH
Default: 0H
Min.: 0H
Max.: FFFFH
Default: 0H
Min.: 0H
Max.: FFFFH
Default: 0H
Min.: 0H
Max.: FFFFH
Default: 0H
Min.: 0H
Max.: FFFFH
Default: 0H
Min.: 0H
Max.: FFFFH
Default: 1
Range: 0, 1
29