5 Installation Procedure
Properly connect all pins and connectors on the option and drive.
Failure to comply could prevent proper operation and damage equipment.
Confirm that all connections are correct after installing the option and connecting peripheral devices.
Failure to comply could damage the option.
Prior to Installing the Option
Prior to installing the option, wire the drive, make necessary connections to the drive terminals, and verify that the drive
functions normally without the option installed. Refer to the instruction manual packaged with the drive for information
on wiring and connecting the drive.
Installing the Option
Refer to the instructions below to install the option.
DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply could result in death
or serious injury. Before installing the option, disconnect all power to the drive. The internal capacitor remains charged even after the
power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric
shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level.
1.
Shut off power to the drive, wait at least five minutes after confirming the DC bus voltage is safe, then loosen the
screw that fastens the front cover in place and remove the front cover. This drive front cover will be replaced by
the option cover. Cover removal varies depending on drive size.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option, drive, and
circuit boards. Failure to comply may result in ESD damage to circuitry.
Figure 5
2.
The remaining installation steps differ based on drive model. Find the drive model number on the drive
nameplate and refer to the step indicated in
Enclosure Type
IP20/Open-Chassis
IP20/UL Type 1
<1>
IP66/UL Type 4X without Filter
IP66/UL Type 4X with Filter
<1> Installing the option on an IP20/UL Type 1 enclosure drive voids UL Type 1 protection while maintaining IP20 conformity.
14
NOTICE
V1000
Figure 5 Remove Front Cover
Table 6
Table 6 Installation Steps Based on Drive Model
Drive Model
CIMR-VAB
CIMR-VAF
CIMR-VAG
CIMR-VAH
YASKAWA ELECTRIC SIEP C730600 70B V1000 Option SI-EP3/V Technical Manual
based on your model number.
Proceed to Step
3.
6.
10.
10.
Page
15
16
18
18