8 Communication
Field(s)
Response Reference
Mirrored from the request.
Response from the slave. In the event that requested services fail, a
Response ID
"not acknowledged" (NAK) response will be indicated.
DO-ID
To be set to 1.
No. of Parameters
Number of parameters that are present in the response.
Format
Refer to
<1>
Number of Values
Number of values following.
<1>
The values of the request.
Values
When there is an odd number of bytes, a zero byte is appended to
<1>
ensure the word structure of the telegram.
<1> Only when Request ID is 0x01 (Request Parameter OK). The Format, Number of Values, and Value Fields are repeated for other parameters.
Error #
0x00
Impermissible parameter number
0x01
Parameter value cannot be changed
0x02
Low or high limit exceeded
0x03
Invalid subindex
0x04
No array
0x05
Incorrect data type
0x06
Setting not permitted (can only be reset)
0x07
Description element cannot be changed
0x09
No description data available
0x0B
No operation priority
0x0F
No text array available
Request cannot be executed because of
0x11
operating mode
0x14
Value impermissible
0x15
Response too long
0x16
Parameter address impermissible
0x17
Illegal format
0x18
Number of values inconsistent
0x19
DO nonexistent
0x65 to 0xFF Manufacturer-specific
0x65
Vendor-specific error
0x66
Request not supported
0x67
Communication error
0x6F
Time-out error
42
Table 25 PROFIdrive Response Header
Description
Table 26
for details.
Table 26 Data Types for Format Field
Code
0x00
0x01 to 0x36
0x37 to 0x3F
0x40
0x41
0x42
0x43
0x44
0x45 to 0xFF
Table 27 PROFIdrive Parameter Request Error Codes
Meaning
Access to unavailable parameter.
Change access to a parameter value that cannot be changed.
Change access with value outside the limits.
Access to unavailable subindex.
Access with subindex to non-indexed parameter.
Change access with value that does not match the data type of the parameter.
Change access with value unequal to 0 when this is not permitted.
Change access to a description element that cannot be changed.
Access to unavailable description (parameter value is available).
Change access rights without rights to change parameters.
Access to text array that is not available (parameter value is available).
Access is temporarily not possible for reasons outside scope of these instructions.
Change access with a value that is within limits but is not permissible for other
long-term reasons (parameter with defined single values).
The length of the current response exceeds the maximum transmittable length.
Illegal value or value that is not supported for the attribute, number of elements,
parameter number or sub-index, or a combination.
Write request: Illegal format or format of parameter data that is not supported.
Write request: Number of values of parameter data does not match number of elements
at the parameter address.
Request to DO, which does not exist.
Vendor-specific error.
Request not supported.
Request cannot be completed because of communication error.
Request aborted due to time-out.
YASKAWA ELECTRIC SIEP C730600 70B V1000 Option SI-EP3/V Technical Manual
Range
1 to 255
Request Param OK (0x01) Request Param NAK
(0x81) Change Param OK (0x02) Change Param NAK
(0x82)
0 to 255
1 to 37
0 to 234
Varies based on value
Type
(Reserved)
Standard data types
(Reserved)
Zero
Byte
Word
Double word
Error
(Reserved)
Used at

Hide quick links: