10 Technical data

Pos: 23.2 /Überschriften/1.1/2-spaltig/D - F/Funktionale Spezifikation @ 1\mod_1148976354843_3101.doc @ 27494

10.1 Functional specifications

Pos: 23.3 /==== Wechsel ein- auf zweispaltig ==== @ 0\mod_1130421847171_3101.doc @ 3828
Change from one to two columns
Pos: 23.4 /Technische Daten / Datenblatt/Druck/Druckmessumformer/265Dx, 265Vx/Messbereich und Messspannengrenzwerte @ 5\mod_1164182285812_3101.doc @ 49207
Measured variable
265Dx :
Differential pressure, vacuum pressure, gauge pressure
265Vx :
Absolute pressure
Measuring range and span limits
Upper
Sensor
Lower range
range limit
code
limit (LRL)
(URL)
1 kPa
-1 kPa
10 mbar
-10 mbar
A
4 in H
O
-4 in H
2
6 kPa
-6 kPa
60 mbar
-60 mbar
C
24 in H
O
-24 in H
2
40 kPa
-40 kPa
400 mbar
-400 mbar
F
160 in H
O
-160 in H
2
250 kPa
-250 kPa
2,500 mbar
-2,500 mbar
L
1,000 in H
2
-1,000 in H
O
2,000 kPa
-2,000 kPa
N
20 bar
-20 bar
290 psi
-290 psi
10,000 kPa
-10,000 kPa
R
100 bar
-100 bar
1,450 psi
-1,450 psi
Change from one to two columns
Pos: 23.6 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
IM/265D/V-EN-02
Minimum span
265Dx
265Vx
0.05 kPa
0.5 mbar
O
0.2 in H
O
2
2
0.2 kPa
2 mbar
O
0.8 in H
O
2
2
0.4 kPa
2 kPa
4 mbar
20 mbar
O
1.6 in H
O
15 mm Hg
2
2
2.5 kPa
12.5 kPa
25 mbar
125 mbar
O
10 in H
O
93.76 mm Hg
2
2
20 kPa
100 kPa
0.2 bar
1 bar
2.9 psi
14.5 psi
100 kPa
1 bar
14.5 psi
Important
The lower range limit (LRL) for 265Vx is absolute 0 for all
measuring ranges.
Span limits
Maximum span = URL = Upper range limit
265Dx
Linear/freely programmable characteristic:
Square root characteristic: Sample setting: 0 ... 400 mbar
265Vx
Linear/freely programmable characteristic:
To optimize performance characteristics, it is recommended that you
select the transmitter sensor with the lowest turndown ratio.
Zero suppression and elevation
(265Vx: Zero suppression only)
The zero position and span can be set to any value within the range
limits listed in the table if:
-
Set span ≥ minimum span
Damping
Adjustable time constant: 0 ... 60 s
This is in addition to the sensor response time.
Second sensor for absolute pressure measurement (
Measuring range:
Warm-up period
According to technical data, ready for operation in ≤ 2.5 s after
switching on the transmitter, with minimum damping.
Insulation resistance
> 100 MΩ at 500 VDC (between terminals and ground)
Pos: 23.5 /==== Wechsel zwei- auf einspaltig ==== @ 0\mod_1130421955859_3101.doc @ 3829
265Dx, 265VS
Technical data
limits, may be adjusted up to ± upper
range limit
Sample setting: -400 ... 400 mbar
(Recommendation for square root function:
At least 10 % of upper range limit
(URL)).
0 ... 400 mbar abs.
41 MPa, 410 bar, 5,945 psi
(0.6 MPa, 6 bar, 87 psi for sensor code A)
Within the range
Sample
setting:
265Dx)
67