5.8

Connecting cable

Pos: 13.24 /Elektrischer Anschluss/Druck/Druckmessumformer/Allgemein/Anschlusskabel @ 3\mod_1157616660609_3101.doc @ 39583
Communication between the transmitter and PC or laptop is only possible if the cabling meets
the following requirements:
It is recommended that shielded, twisted pair cables are used.
The minimum wire diameter depends on the line length.
Line lengths up to 1,500 m (4,921 ft): 0.51 mm (0.02 inch)
Line lengths above 1,500 m (4,921 ft): 0.81 mm (0.03 inch)
The maximum line length is limited.
Dual-core cable: 3,000 m (9,842 ft)
Multi-core cable: 1,500 m (4,921 ft)
The actual possible line length of the electrical circuit depends on the total capacitance and
resistance, and can be estimated using the following formula:
65
=
L
L
R
C
C
f
Avoid routing cables with other electrical cables (with inductive load, etc.) or near large electrical
equipment.
Pos: 13.25 /Erdung/Druck/Druckmessumformer/Allgemein/Hinweis zur Erdung der Abschirmung @ 2\mod_1149837270140_3101.doc @ 28949
Important
The shielding for the connecting cable should only be grounded at one side.
Pos: 13.26 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
IM/265D/V-EN-02
6
+
×
10
C
10000
f
×
R
C
C
= Line length in meters
= Total resistance in Ω (ohms)
= Line capacitance in pF/m
= Maximum internal capacitance of the HART field devices located in the circuit, in pF
265Dx, 265VS
Electrical connection
35