Parameter Description - ABB 265DS Operating Instruction

265d series differential pressure transmitter
Table of Contents

Advertisement

Configuration
Pos: 19.24 /Überschriften/1.1.1/1-spaltig/Parameterbeschreibung @ 1\mod_1147935919250_3101.doc @ 12649
8.6.1

Parameter description

Pos: 19.25 /Konfiguration, Parametrierung/Druck/Druckmessumformer/Druckmessumformer 265Dx, 265Vx/Parameterbeschreibung @ 5\mod_1164102970328_3101.doc @ 49035
8.6.1.1
"VIEW" parameter
Temporary display of display values 1 to 9 (setting is volatile)
The following measured values can be set:
Output signal in physical unit
265Dx: Current measured value for differential pressure, or variable derived from this, such
as flowrate / level, with customized unit in each case
265Vx: Current measured value for absolute pressure; corresponds to "OUT" with
PROFIBUS PA
Setting changes under "OUT 0 %" and "OUT 100 %"; desired unit under "UNIT_OUT"
Percentage value of output signal
Output current (not with fieldbus transmitters)
Static pressure
Pressure/differential pressure
Current pressure/differential pressure value in range between lower and upper range limit
values set
Setting changes under "GET 0 % / 100 %" or "SET 0 % / 100 %"; desired unit under
"UNIT_p/dp"
Sensor temperature
8.6.1.2
"GET 0 %" and "GET 100 %" parameters
Setting with applied pressure
8.6.1.3
"SET 0 %" and "SET 100 %" parameters
Setting without applied pressure
8.6.1.4
"SHIFT ZERO" parameter
Zero correction (e.g. oblique sensor)
8.6.1.5
"SHIFT OFFSET" parameter
Offset shift (parallel shift; see also "Configuration")
8.6.1.6
"OUT 0 %" and "OUT 100 %" parameters
Setting for output variables (including "VIEW", display code no.1, and "DISPLAY", display code
no. 1)
58
265Dx, 265VS
IM/265D/V-EN-02