Pos: 13.6 /Überschriften/1.1/1-spaltig/D - F/Elektrischer Anschluss im Kabelanschlussraum @ 1\mod_1147680681593_3101.doc @ 10995
5.2

Electrical connection in the cable connection area

Pos: 13.7 /Elektrischer Anschluss/Druck/Druckmessumformer/Druckmessumformer 265Dx, 265Vx/Elektrischer Anschluss im Kabelanschlussraum @ 5\mod_1164013909046_3101.doc @ 48769
Fig. 7: Cable connection area (depiction of DIN housing)
1 Ground/equipotential bonding terminals
2 EEx d locking screw
3 Output signal / power supply
4 Screw terminals for 0.5 ... 2.5 mm
(AWG 20 ... AWG 14)
The electrical connection is established in the connection area. The housing cover must be
unscrewed for this purpose.
The M20 x 1.5 cable glands, which are supplied by the manufacturer, are screwed only loosely
into the electronics housing. In order to achieve protection type IP 67, the glands must be
screwed in using a suitable tool (hexagon head, SW 22) until they are hand-tight.
Delivery scope
HART devices
M20 x 1.5 cable entry
1/2 - 14 NPT
Han 8D (8U) device plug
Bus devices (PA/FF)
M20 x 1.5 cable entry
1/2 - 14 NPT
M12 x 1 connector
7/8" connector
IM/265D/V-EN-02
2
1
6
2
265Dx, 265VS
Electrical connection
3
5
4
5 Test terminals for 4 ... 20 mA (not
available with fieldbus transmitters)
6 Cable entry (e.g., via M20 x 1.5)
Gland/mating plug
Plastic cable gland
(6 ... 12 mm clamping area)
Not included in delivery scope
Socket connector
Gland/mating plug
Metal cable gland
(6 ... 12 mm clamping area)
Not included in delivery scope
Not included in delivery scope
Not included in delivery scope
M00158
29