Setting The Damping Value; Correcting The Zero Shift / Oblique Sensor; Setting The Lower And Upper Range Values - ABB 265DS Operating Instruction

265d series differential pressure transmitter
Table of Contents

Advertisement

8.8.2

Setting the damping value

Menu path:
"Configure_Differential Pressure Measurement_Output"
Enter the desired value in the "Damping" line of the "Output parameter" field.
8.8.3

Correcting the zero shift / oblique sensor

Menu path:
"Configure_Differential Pressure Measurement_Process Variable"
Press the "Adjust" button in the "Oblique sensor" field.
Calibration is performed immediately and saved to the transmitter's non-volatile memory.
8.8.4

Setting the lower and upper range values

Menu path:
"Configure_Differential Pressure Measurement_Process Variable"
The "Scaling" field offers two setting options:
1.
Enter the desired values in the "Lower range value" and/or "Upper range value" input fields.
2.
For setting purposes, apply the pressure for the "lower range value" and "upper range value" to
the device. Make sure that the measuring limits are not exceeded.
Reducing stations with adjustable pressure and reference displays can be used as pressure
transducers.
When making the connection, please ensure that there are no residual fluids (for gaseous
testing materials) or air bubbles (for fluid testing materials) in the connection lines, since these
can lead to errors during inspection.
The measuring error for the pressure transducer should be at least three times smaller than the
desired measuring error for the pressure transmitter.
Pos: 20 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
IM/265D/V-EN-02
Enter value (Value Input)
Apply PV (Process Pressure Transfer)
265Dx, 265VS
Configuration
63

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

265dr265dc265vs

Table of Contents