6.3

Correcting the lower range value / zero shift

Pos: 15.10 /Inbetriebnahme/Druck/Druckmessumformer/Druckmessumformer 265Dx, 265Vx/Korrektur Messanfang / Messwerkschieflage @ 5\mod_1164017624328_3101.doc @ 48874
During installation of the transmitter, zero shifts caused by mounting (e.g., a slightly oblique
mounting position due to a remote seal, etc.) may occur; these must be corrected.
Important
The transmitter must have reached its operating temperature (approx. 5 min. after startup, if
the transmitter has already reached the ambient temperature) in order to perform zero shift
correction. The correction must be made at dp = 0.
There are two options (points A or B) for correcting the 4 ... 20 mA output signal directly on the
pressure transmitter:
Important
The button unit must be available for this purpose. Operating the buttons using a magnetic
screwdriver is not permitted.
A. Set lower range value
1. Apply the lower range value pressure (4 mA) from the process or from a pressure
transducer. The pressure must be stable and applied with a high level of accuracy << 0.05 %
(observing the set damping value).
2. Press the "0 %" button on the pressure transmitter. The output signal is set to 4 mA. The
span remains unchanged.
Important
A lower range value set using this method will be stored in the non-volatile memory < 25 s
(HART), < 110 s (PROFIBUS PA), and < 15 s (FOUNDATION Fieldbus) when the
"0 %" button is pressed for the final time.
B. Correct the zero shift
1. Use the control buttons "M" and "+", together with the LCD display (installed as an option), to
call up the "SHIFTZERO" menu item.
2. The correction is made by pressing the "M" button (refer to the section "Configuration with
the LCD display").
3. Put the transmitter into operation as described at the beginning of this section.
Important
The procedure described in "A" above does not affect the physical pressure shown; it only
corrects the analog output signal. For this reason, the analog output signal may differ from the
physical pressure shown on the digital display or the communication tool.
To avoid this discrepancy, correct the zero position shift (zero shift) via the graphical user
interface (DTM).
Menu path: "Configure_Differential Pressure Measurement_Process Variable"
However, the lower range value must not have been corrected already using the "0 %" button.
Pos: 15.11 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
IM/265D/V-EN-02