PROFIBUS PA differential pressure transmitter

Pos: 13.28 /Elektrischer Anschluss/Druck/Druckmessumformer/Allgemein/PROFIBUS PA-Druckmessumformer @ 2\mod_1149837797671_3101.doc @ 28991
PROFIBUS PA transmitters are designed to be connected to the DP / PA segment coupler /
linking device. The permissible terminal voltage is within the range of 10.2 ... 32 VDC.
Use of a shielded cable is recommended. The shielding is bonded by means of the metal cable
gland.
Important
The transmitter must be grounded.
The switch-on behavior corresponds to Draft DIN IEC 65C/155/CDV of June 1996. If the
transmitter is operated on an Ex segment coupler / linking device in accordance with
DIN EN 61 158-2 of October 1994, time-dependent current limiting may cause the maximum
number of devices to be reduced.
The "OUT" variable is transmitted cyclically. This consists of the output value and 1 byte of
status information. The output value is transmitted with 4 bytes as an IEEE 754 floating-point
type.
For additional information on PROFIBUS PA - including the subject "Identification numbers" -
please
suggestions 10/63-0.40". These can be obtained from the Internet site www.abb.com; additional
information is also available at www.profibus.com.
Pos: 14 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
36
refer
to
"Additional
265Dx, 265VS
notes 41/15-110"
and
the
data
sheet
"Installation
IM/265D/V-EN-02