Pos: 15.17 /Überschriften/1.1/1-spaltig/M - O/Montage / Demontage des LCD-Anzeigers @ 1\mod_1148889545031_3101.doc @ 18066
6.6
Installing/Removing the LCD display
Pos: 15.18 /Inbetriebnahme/Druck/Druckmessumformer/Allgemein/Montage / Demontage des LCD-Anzeigers @ 4\mod_1162548621765_3101.doc @ 43744
1. Unscrew the housing cover of the electronics area (refer to the figure "Securing the housing
cover" in the next section).
Important
With an EEx d design, please refer to the section "Securing the housing cover with EEx d".
2. Attach the LCD display. Depending on the mounting position of the pressure transmitter, the
LCD display may be attached in four different positions. This enables ± 90 ° or ± 180 °
rotations.
Important
In the case of LCD displays with backlighting (optional), a 3-wire cable with a plug is located at
the rear of the LCD display. Connect this plug to the 3-pin terminal in the electronics area
before attaching the display (see Fig. 15).
3. If the 3-pin terminal strip is equipped with a jumper (fieldbus transmitters do not have
jumpers), remove this and insert it in the "jumper holder".
4. Screw the LCD display in place using the two screws.
5. Retighten the housing cover until it is hand-tight.
Important
If necessary, refer to the section "Securing the housing cover with EEx d".
IM/265D/V-EN-02
265Dx, 265VS
Commissioning
41