Parameter Description Hart® (For Hart®-Devices To Sw-Rev.: 01.03); Menu: Device Setup - ABB TTF300 Operating Instruction

Field-mount temperature transmitter
Hide thumbs Also See for TTF300:
Table of Contents

Advertisement

54
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. I
... 10 Operation
Parameter description HART® (for HART®-devices to SW-Rev.: 01.03)

Menu: Device Setup

Menu / parameter
... / Device Setup
Write protection
Input Sensor 1
Input Sensor 2
Input / output assignment
Measured range
Damping
Factory reset
... / Device Setup / Input Sensor 1
... / Device Setup / Input Sensor 2
Sensor Type
Description
Activates write protection for the entire device
Yes: locked
Input combination:≠ 0110
No: unlocked
Input combination:0110
Select the 'Input Sensor 1' submenu.
Select the 'Input Sensor 2' submenu.
Input / output assignment selects the inputs that are mapped to the current output
Sensor 1
Sensor 2
Difference (S1-S2)
Difference (S2-S1)
Meanvalue
Electr. Meas. S1
Electr. Meas. S2
Redundancy
Temp. Electronics
Select the 'Measured range' submenu.
Configurable τ 63% output signal damping value
Value range:0 to 100 s
Resets configuration data, adjustment data trim high / low and DAC adjustment values to factory settings.
Yes / OK
Selects sensor type:
Pt100 (IEC751):Pt100 resistance thermometer (IEC 751)
Pt1000 (IEC751):Pt1000 resistance thermometer (IEC 751)
Type K TC (IEC584):Thermocouple type K (IEC 584)
Type B TC (IEC584):Thermocouple type B (IEC 584)
Type C TC (ASTME988):Type C thermocouple (IEC584)
Type D TC (ASTME988):Thermocouple type D (ASTME 988)
Type E TC (IEC584):Thermocouple type E (IEC 584)
Type J TC (IEC584):Type J thermocouple (IEC584)
Type N TC (IEC584):Thermocouple type N (IEC 584)
Type R TC (IEC584):Type R thermocouple (IEC584)
Type S TC (IEC584):Type S thermocouple (IEC584)
Type T TC (IEC584):Type T thermocouple (IEC584)
Type L TC (DIN43710):Type L thermocouple (DIN43710)
Type U TC (DIN43710):Type U thermocouple (DIN43710)