Fuses
UL compliance
To comply with UL/cUL approvals, pre-fuses according to the table below must be used.
200-240 V
VLT
Bussmann
6002
KTN-R10
6003
KTN-R15
6004
KTN-R20
6005
KTN-R25
6006
KTN-R30
6008
KTN-R50
6011, 6016
KTN-R60
6022
KTN-R80
6027, 6032
KTN-R125
6042
FWX-150
6052
FWX-200
6062
FWX-250
380-460 V
Bussmann
6002
KTS-R6
6003, 6004
KTS-R10
6005
KTS-R15
6006
KTS-R20
6008
KTS-R25
6011
KTS-R30
6016, 6022
KTS-R40
6027
KTS-R50
6032
KTS-R60
6042
KTS-R80
6052
KTS-R100
6062
KTS-R125
6072
KTS-R150
6102
FWH-220
6122
FWH-250
6152*
FWH-300/170M3017
6172*
FWH-350/170M3018
6222*
FWH-400/170M4012
6272*
FWH-500/170M4014
6352*
FWH-600/170M4016
6402
170M4017
6502
170M6013
6552
170M6013
6602
170M6013
* Circuit Breakers manufactured by General Electric, Cat .No. SKHA36AT0800, with the rating plugs listed
below can be used to meet UL requirement.
6152
rating plug No.
6172
rating plug No.
6222
rating plug No.
6272
rating plug No.
6352
rating plug No.
38
SIBA
Littel fuse
5017906-010
KLN-R10
5017906-016
KLN-R15
5017906-020
KLN-R20
5017906-025
KLN-R25
5017906-032
KLN-R30
5012406-050
KLN-R50
5014006-063
KLN-R60
5014006-080
KLN-R80
2028220-125
KLN-R125
2028220-150
L25S-150
2028220-200
L25S-200
2028220-250
L25S-250
SIBA
Littel fuse
5017906-006
KLS-R6
5017906-010
KLS-R10
5017906-016
KLS-R16
5017906-020
KLS-R20
5017906-025
KLS-R25
5012406-032
KLS-R30
5014006-040
KLS-R40
5014006-050
KLS-R50
5014006-063
KLS-R60
2028220-100
KLS-R80
2028220-125
KLS-R100
2028220-125
KLS-R125
2028220-160
KLS-R150
2028220-200
L50S-225
2028220-250
L50S-250
2028220-315
L50S-300
2028220-315
L50S-350
206xx32-400
L50S-400
206xx32-500
L50S-500
206xx32-600
L50S-600
2061032-700
2063032-900
2063032-900
2063032-900
SRPK800 A 300
SRPK800 A 400
SRPK800 A 400
SRPK800 A 500
SRPK800 A 600
®
VLT
6000 HVAC Series
Ferraz-Shawmut
ATM-R10 or A2K-10R
ATM-R15 or A2K-15R
ATM-R20 or A2K-20R
ATM-R25 or A2K-25R
ATM-R30 or A2K-30R
A2K-50R
A2K-60R
A2K-80R
A2K-125R
A25X-150
A25X-200
A25X-250
Ferraz-Shawmut
ATM-R6 or A6K-6R
ATM-R10 or A6K-10R
ATM-R16 or A6K-16R
ATM-R20 or A6K-20R
ATM-R25 or A6K-25R
ATM-R30 or A6K-30R
A6K-40R
A6K-50R
A6K-60R
A6K-80R
A6K-100R
A6K-125R
A6K-150R
A50-P225
A50-P250
A50-P300
A50-P350
A50-P400
A50-P500
A50-P600
6,9URD31D08A0700
6,9URD33D08A0900
6,9URD33D08A0900
6,9URD33D08A0900
MG.61.A5.02 - VLT is a registered Danfoss trademark
Need help?