Danfoss VLT 6000 series Operating Instructions Manual page 142

Hvac frequency converters
Hide thumbs Also See for VLT 6000 series:
Table of Contents

Advertisement

Warnings
A warning will flash in line 2, while an explanation
is given in line 1.
DC LINK VOLTAGE LOW
WARN. 6
WARNING 1
Under 10 V (10 VOLT LOW)
The 10 V voltage from terminal 50 on the
control card is below 10 V.
Remove some of the load from terminal 50, as the 10
Volts supply is overloaded. Max. 17 mA/min. 590 .
WARNING/ALARM 2
Live zero fault (LIVE ZERO ERROR)
The current or voltage signal on terminal 53, 54 or
60 is below 50% of the value preset in parameter
309, 312 and 315 Terminal, min. scaling.
WARNING/ALARM 4
Mains imbalance (MAINS IMBALANCE)
High imbalance or phase missing on the supply side.
Check the supply voltage to the frequency converter.
Alarm/warning
limits:
VLT 6000 HVAC
Undervoltage
Voltage warning low
Voltage warning
high
Overvoltage
1) VLT 6102-6652.
The voltages stated are the intermediate circuit voltage of the frequency converter with
a tolerance of ± 5 %. The corresponding mains voltage is the intermediate circuit
voltage divided by 1,35.
142
SETUP
1
3 x 200 - 240 V
3 x 380 - 460 V
[VDC]
211
222
384
425
®
VLT
6000 HVAC Series
Alarms
If an alarm is given, the present alarm number
will be shown in line 2. Lines 3 and 4 of the
display will offer an explanation.
TRIP (RESET)
ALARM:12
CURRENT LIMIT
WARNING 5
Voltage warning high (DC LINK VOLTAGE HIGH)
The intermediate circuit voltage (DC) is higher than
Voltage warning high, see table below. The controls
of the frequency converter are still enabled.
WARNING 6
Voltage warning low (DC LINK VOLTAGE LOW)
The intermediate circuit voltage (DC) is lower than
Voltage warning low, see table below. The controls
of the frequency converter are still enabled.
WARNING/ALARM 7
Overvoltage (DC LINK OVERVOLT)
If the intermediate circuit voltage (DC) is higher than
the Overvoltage limit of the inverter (see table below),
the frequency converter will trip after a fixed period.
The length of this period depends on the unit.
3 x 525-600 V
[VDC]
[VDC]
402
557
423
585
769
943
855
975
MG.61.A5.02 - VLT is a registered Danfoss trademark
SETUP
SETUP
1
1
1)
3 x 525-600 V
[VDC]
553
585
1084
1130