Warning:
Touching the electrical parts may be fatal - even after the equipment has been
disconnected from mains.
Using VLT 6002 - 6005, 200-240 V: Wait at least 4 minutes
Using VLT 6006 - 6062, 200-240 V: Wait at least 15 minutes
Using VLT 6002 - 6005, 380-460 V: Wait at least 4 minutes
Using VLT 6006 - 6072, 380-460 V: Wait at least 15 minutes
Using VLT 6102 - 6352, 380-460 V: Wait at least 20 minutes
Using VLT 6402 - 6602, 380-460 V: Wait at least 40 minutes
Using VLT 6002 - 6006, 525-600 V: Wait at least 4 minutes
Using VLT 6008 - 6027, 525-600 V: Wait at least 15 minutes
Using VLT 6032 - 6072, 525-600 V: Wait at least 30 minutes
Using VLT 6102 - 6402, 525-600 V: Wait at least 20 minutes
Using VLT 6502 - 6652, 525-600 V: Wait at least 30 minutes