Technical data, mains supply 3 x 200-240V
According to international requirements
Output current
Output power (240 V)
Typical shaft output
Typical shaft output
Max.
cross-section to
motor
and DC-bus
Max. input current
Max. cable
cross-section power
Max. pre-fuses
Efficiency
Weight IP 20
Weight IP 54
Power loss at
max. load. [W]
Enclosure
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Current ratings fulfill UL requirements for 208-240 V.
26
VLT type
4)
I
VLT,N
I
(60 s) [A]
VLT, MAX
S
[kVA]
VLT,N
P
[kW]
VLT,N
P
[HP]
VLT,N
2
cable
[mm
]/[AWG]
(200 V) (RMS)I
2
[mm
]/[AWG]
1)
[-]/UL
3)
[kg]
[kg]
Total
VLT type
®
VLT
6000 HVAC Series
6002
6003
6004
[A]
6.6
7.5
10.6
7.3
8.3
11.7
2.7
3.1
4.4
1.1
1.5
2.2
1.5
2
3
4/10
4/10
4/10
L,N
6.0
7.0
10.0
[A]
2 )
4/10
4/10
4/10
[A]
16/10
16/15
25/20
0.95
0.95
0.95
7
7
9
11.5
11.5
13.5
76
95
126
IP 20 / IP 54
MG.61.A5.02 - VLT is a registered Danfoss trademark
6005
6006
6008
6011
12.5
16.7
24.2
30.8
13.8
18.4
26.6
33.9
5.2
6.9
10.1
12.8
3.0
4.0
5.5
7.5
4
5
7.5
10
4/10
10/8
16/6
16/6
12.0
16.0
23.0
30.0
4/10
4/10
16/6
16/6
25/25
35/30
50
60
0.95
0.95
0.95
0.95
9
23
23
23
13.5
35
35
38
172
194
426
545