322 Terminal 45, output, pulse scaling
(AO 45 PULS SCALE)
Value:
1 - 32000 Hz
Function:
This parameter allows scaling of the pulse output signal.

Relay outputs

Relay outputs 1 and 2 can be used to give the
present status or a warning.
Relay 1
1 - 3 break, 1 - 2 make
Max. 240 V AC, 2 Amp.
The relay is placed with
the mains and motor
terminals.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.61.A5.02 - VLT is a registered Danfoss trademark
VLT
Description of choice:
Set the desired value.
5000 Hz
Relay 2
4 - 5 make
Max. 50 V AC, 1 A, 60 VA.
Max. 75 V DC, 1 A, 30 W.
The relay is placed on the control card,
see Electrical installation, control cables.
®
6000 HVAC Series
111