Danfoss VLT 6000 series Operating Instructions Manual page 129

Hvac frequency converters
Hide thumbs Also See for VLT 6000 series:
Table of Contents

Advertisement

Description of choice:
Set the required time delay before trip and
setting the output.
483 Dynamic DC link compensation
(DC LINK COMP.)
Value:
Off
On
Function:
The frequency converter includes a feature, which
ensures that the output voltage is independent of
any voltage fluctuation in the DC link, e.g. caused
by fast fluctuation in the mains supply voltage. The
benefit is a very steady torque on motor shaft (low
torque ripple) under most mains conditions.
Description of choice:
In some cases this dynamic compensation can
cause resonance's in the DC link and should then
be disabled. Typical cases are where a line choke or
a passive harmonic filter (e.g. filters AHF005/010)
is mounted in the mains supply to the frequency
converter to suppress harmonics. Can also occur
on mains with low short circuit ratio.
500 - 566
Serial communication
Value:
All information concerning the use of RS 485 serial
interface is not included in this manual. Please contact
Danfoss and ask for the VLT 6000 HVAC Design Guide.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.61.A5.02 - VLT is a registered Danfoss trademark
®
VLT
6000 HVAC Series
[0]
[1]
129