Power Options

Overview

6.4.1
The 7SR46 Argus Relay can be powered on by using the following sources:

Auxiliary power supply

CT input

USB power
Battery
The 7SR46 Argus relay is powered primarily from auxiliary power supply even if all other power sources are
available. In the absence of auxiliary power supply, the relay is powered through phase currents. It is also
referred to as CT power.
In the absence of both auxiliary power and phase currents, the relay is powered on by USB power or battery.
In the absence of auxiliary power supply, phase currents, and USB power, the relay can be powered on by
battery only.
Table 6-1
Power Source
Auxiliary Power Supply
CT Input
USB Power
Battery
6.4.2
Auxiliary Power Supply
When the 7SR46 Argus Relay is powered with auxiliary power supply, all the protection and measuring algo-
rithms and RS485 communication (Rear port) are active.
6.4.3
CT Input
When the 7SR46 Argus Relay is powered through phase current transformers and the auxiliary voltage is
absent, all the protection and measuring algorithms are active 0.8 ⋅ I
RS485 communication is operational when current above 1.62 ⋅ I
Table 6-2
Peripherals
Binary output, binary input,
pulse output, flag output,
local flag, and external trip
input
RS-485 communication
LCD Backlight
Refer to
6.4.3 CT Input
for corresponding current ratings.
1
2
Is operational only under Maintenance menu.
Reyrolle, Operating, Manual
C53000-B7040-C103-1, Edition 10.2022
Peripheral Operations in Different Power Sources
Peripherals Operational
Binary input, binary output, pulse output, remote flag, local flag, LED,
external trip input, RS-485 communication, LCD backlight
Binary input, binary output, pulse output, remote flag, local flag, LED,
external trip input
Binary input, binary output, LED, LCD backlight, pulse output
flag
, and local flag
2
Binary input, binary output, LED, LCD backlight, resetting local flag
Minimum Current Requirements for Peripheral Operations in Self-Powered Mode
1-Phase (⋅ I
0.8
1.62
-
1
, RS-485 communication
2
smin
(1-phase) or 0.6 ⋅ I
smin
)
3-Phase (⋅ I
smin
0.4
0.6
1.62
In Service Operation

6.4 Power Options

1
, LCD backlight
1
2
, remote
(1-phase) and 0.4 ⋅ I
(3-phase).
smin
(3-phase).
smin
)
smin
57

Advertisement

Table of Contents
loading

Table of Contents