9 UTILITY OPERATIONS

9.2.3 Board information screen operation

Item
Channel
Own Station Information
Board Set button
Mode
Transmission Speed
9 - 6
The Board information screen is used to set and display various information about the
installed MELSECNET/H board.
Sets a channel (MELSECNET/H board) to be used.
Displays information and changes setting on the host.
Resets the MELSECNET/H board to renew the information of the MELSECNET/H board
selected in Channel.
Performs mode setting for the MELSECNET/H board, and displays the present value.
Mode
Online (auto. reconnection)
Offline
Forward loop
Reverse loop
Test between master station
Test between slave station
Self-loopback test
Internal self-loopback test
H/W test
Selects the transmission speed.
When the Q80BD-J71LP21G, Q80BD-J71LP21GE and Q80BD-J71BR11 is used and
when "MNET10 Mode" is selected in the NET Mode, "25 Mbps" cannot be selected.
Transmission speed
10 Mbps
25 Mbps
Content
Used for normal communication.
Enters the state in which there is no connection to the
network.
Check the forward loop status.
Check the reverse loop status.
Perform station to station test.
(Select at control station)
Perform station to station test
(Select at normal station)
Check the hardware including the cable and
communication circuit for transmission system by the
MELSECNET/H board.
Check the hardware including the communication circuit
for transmission system by the MELSECNET/H board.
Check the hardware of the MELSECNET/H board.
Description
Selected when the MELSECNET/H (10 Mbps) is connected.
Selected when the MELSECNET/H (25 Mbps) is connected.
MELSEC
Description
9 - 6