Address
Byte 5
LOAD_PREPARE
LOAD_VAL
Bytes 6 to 7
Not used for modified user interface
1
Notes on the Control Bits
Table 2-26
Notes on the Control Bits
Control bits
Notes
CTRL_SYN
You use this bit to enable synchronization.
EXTF_ACK
Error acknowledgment
The error bits must be acknowledged with the EXTF_ACK control bit after the cause is removed. (see
figure below)
LOAD_PREPARE
Load counter preparatory (see figure below)
The value from bytes 0 to 3 is applied as the load value.
LOAD_VAL
The value from bytes 0 to 3 is loaded directly as the new count value.
RES_STS
Start resetting of status bit
The status bits are reset through the acknowledgment process between the RES_STS bit and the
RES_STS_A bit. (see figure below)
SW GATE
The SW gate is opened/closed via the control interface with the SW_GATE bit.
Technological Functions
Operating Instructions, 02/2007, A5E00124867-05
Assignment
Bit 7:
Reserve = 0
Bit 6:
Reserve = 0
Bit 5:
Reserve = 0
Bit 4:
Reserve = 0
Bit 3:
Reserve = 0
Bit 2:
Reserve = 0
Bit 1:
Load counter preparatory
Bit 0:
Load counter direct
Reserve = 0
1
1Count24V/100kHz
2.8 Position Detection