2PULSE
5.1 Product Overview
Functions
• Direct control of the digital output by means of the control program
• Programmable behavior for CPU/master STOP
• Error detection/diagnostics (short circuit of the digital output and encoder supply)
Configuration
You can use either of the following to configure the 2PULSE:
• A GSD file (http://www.ad.siemens.de/csi/gsd)
or
• STEP 7 V5.0 SP3 and later.
Restrictions with the 2PULSE electronic module (6ES7 138-4DD00-0AB0)
Note
Restrictions for the 2PULSE module with IM151-7 CPU, IM151-1 HIGH FEATURE or
IM 151-1 BASIC:
With the IM 151-7 CPU, you must use STEP 7 V5.1, Service Pack 1, Hotfix 1 or higher for
configuration.
You cannot enable the group diagnostics parameter in the configuration if you use the
2PULSE module.